Sales hotline:13775032303
Specification
Cells Per Unit: 6
Voltage Per Unit: 12 V
Capacity: 120W @ 15-minute-rate to 1.67V per cell @ 25°C (77°F)
Weight: Approximately 10.2 Kg (22.48 lbs)
Maximum Discharge Current: 225A (5 Sec)
Internal Resistance: Approximately 8.2 mΩ
Operating Temperature Range:
- Discharge: -15℃~50℃ (5°F~122°F)
- Charge: -15℃~40℃ (5°F~104°F)
- Storage: -15℃~40℃ (5°F~104°F)
Nominal Operating Temperature Range: 25°C ± 3°C (77°F ± 5°F)
Float Charging Voltage: 13.5 to 13.8 VDC/Unit Average at 25°C (77°F)
Recommended Maximum Charging Current Limit: 12.0 A
Equalization and Cycle Service: 14.4 to 15.0 VDC/Unit Average at 25°C (77°F)
Self Discharge: It should be more than 75% of the capacity that before storage after stocked for 6 months at ambient temp. 25°C
Terminal: I1-Thread lead alloy recessed terminal to accept M5 bolt
Container Material: ABS(UL94-HB) & Flammability resistance of(UL94-V0) can be available upon request.
HR series
HR 12120W
Valve Regulated Lead Acid Battery
Maintenance-Free Sealed Lead Acid Battery.
Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99%.
General Design for Standby Power Applications
【Design Life】【 Float Charging Voltage】
Up to 5 Years in Standby Service at 25℃13.5 ~ 13.8 VDC/Unit at 25℃ (77℉)
Eurobat (20℃) : 3-5 YEARS STANDARD COMMERCIAL【Equalization Charging Voltage 】
【 Operating Temperature Range】14.4 ~ 15.0 VDC/Unit at 25℃ (77℉)
Nominal Operating Temperature : 25℃(77℉)【 Self Discharge】
Discharge : -15℃ ~ 50℃ (5℉~122℉)Less than 10% after 90 days, can be stored up to 6 months at 25℃ (77℉);
Charge: -15℃ ~ 40℃ (5℉~104℉)Fully recharging is required before usage, and charged sooner if stored
Storage: -15℃ ~ 40℃ (5℉~104℉)at higher temperature than 25℃ (77℉).
SpecificationDesign according with IEC 61056-1/2:2012
Nominal Voltage12V (6 cells per unit)
Nominal Capacity120W @15min-rate to 1.67V per cell @25℃ (77℉)
WeightApprox. 10.20 Kg (22.48 lbs)
Maximum Discharge Current225A (5sec)
Internal ResistanceApprox. 8.2 mΩ
Short Circuit Current928A
Maximum Charge Current12A
Terminal typesI1 terminal to accept M5 bolt
Terminal tightening torque30.4±6.1 Kgf·cm / 26.4±5.3 Lbf·in / 3.0±0.6 N·m
Container MaterialABS (UL 94-HB) & Flame Retardant (94-V0) available upon request
Length (L)166.0±2.0mm6.54±0.08inch
Width (W)125.0±1.5mm4.92±0.06inch
Dimensions
Container Height (h)175.0±2.0mm6.89±0.08inch
Overall Height (H)175.0±2.0mm6.89±0.08inch
Constant Current Discharge Characteristics Unit: A (25℃, 77℉)
F.V/Time2MIN4MIN5MIN6MIN8MIN10MIN15MIN20MIN30MIN45MIN60MIN90MIN
1.60V16914813512510794.270.556.141.230.424.516.8
1.67V15313512411510088.967.053.639.729.624.016.6
1.70V14612811710995.585.665.352.539.229.223.716.4
1.75V13211710810188.980.262.050.437.828.323.116.2
1.80V11710597.291.281.373.358.348.036.027.122.215.8
1.85V10092.586.882.474.367.354.345.734.626.021.215.2
Constant Power Discharge Characteristics Unit: W (25℃, 77℉)
F.V/Time2MIN4MIN5MIN6MIN8MIN10MIN15MIN20MIN30MIN45MIN60MIN90MIN
1.60V174516221507141911991030771621462348284197
1.67V16081495139313151119975 738600453341279194
1.70V15391427133312601084947 724590447337276193
1.75V14121306122411611012895 701578435329270190
1.80V1273118111131060944 853 676561418319263186
1.85V110010451001966 877 805 648536402307253181
0
Contact: Sir SHU
Phone: 13775032303
Tel: 4001177032
Email: 13775032303@139.com
Add: Room 3208, Floor 2, Rongyu Building, No. 780 Wanhangdu Road, Jing'an District, Shanghai