Sales hotline:13775032303
Specification
Cells Per Unit: 6
Voltage Per Unit: 12 V
Capacity: 90 W @ 15-minute rate, down to 1.67V per cell @ 25°C (77°F)
Weight: Approximately 6.80 kg (14.99 lbs)
Maximum Discharge Current: 300A (5 seconds)
Internal Resistance: Approximately 9.9 mΩ
Operating Temperature Range: Discharge: -15°C~50°C (5°F~122°F)
Charge: -15°C~40°C (5°F~104°F)
Storage: -15°C~40°C (5°F~104°F)
Nominal Operating Temperature Range: 25°C ± 3°C (77°F ± 5°F)
Float Charging Voltage: Average of 13.5 to 13.8 VDC/unit at 25°C (77°F)
Recommended Maximum Charging Current Limit: 9 A
Equalization and Cycle Service: Average of 14.4 to 15.0 VDC/unit at 25°C (77°F)
Self Discharge: It should be more than 75% of the capacity before storage after being stored for 6 months at an ambient temperature of 25°C
Terminal: I1-Thread lead alloy recessed terminal to accept M5 bolt
Container Material: ABS(UL94-HB), Flammability resistance of(UL94-V0) can be available upon request.
HR series
HR 1290W
Valve Regulated Lead Acid Battery
Maintenance-Free Sealed Lead Acid Battery.
Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99%.
GeneralDesign for Standby Power Applications
【Design Life】
Up to 5 Years in Standby Service at 25℃
Eurobat (20℃) : 3-5 YEARS STANDARD COMMERCIAL
【Operating Temperature Range】
Nominal Operating Temperature: 25℃ (77℉)
Discharge: -15℃ ~ 50℃ (5℉~122℉) Charge: -15℃ ~ 40℃ (5℉~104℉) Storage: -15℃ ~ 40℃ (5℉~104℉)【Float Charging Voltage】
13.5 ~ 13.8 VDC/Unit at 25℃ (77℉)
【Equalization Charging Voltage】
14.4 ~ 15.0 VDC/Unit at 25℃ (77℉)
【Self Discharge】
Less than 10% after 90 days, can be stored up to 6 months at 25℃ (77℉);
Fully recharging is required before usage, and charged sooner if stored at higher temperature than 25℃ (77℉).
SpecificationDesign according with IEC 61056-1/2:2012
Nominal Voltage12V (6 cells per unit)
Nominal Capacity90W @ 15min-rate to 1.67V per cell @ 25℃ (77℉)
WeightApprox. 6.60 Kg (14.55 lbs) Maximum Discharge Current300A (5sec)
Internal ResistanceApprox. 9.9 mΩ
Short Circuit Current836A
Maximum Charge Current9.0A
Terminal typesI1 terminal to accept M5 bolt
Terminal tightening torque30.4±6.1 Kgf∙cm / 26.4±5.3 Lbf∙in / 3.0±0.6 N∙m
Container MaterialABS (UL 94-HB) & Flame Retardant (94-V0) available upon request
Length (L)181.0±2.0 mm7.13±0.08 inch
Width (W)76.2±2.0 mm3.00±0.08 inch
Dimensions
Container Height (h)167.0±2.0 mm6.57±0.08 inch
Overall Height (H)167.0±2.0 mm6.57±0.08 inch
Constant Current Discharge Characteristics Unit: A (25℃, 77℉)
F.V/Time2MIN4MIN5MIN6MIN8MIN10MIN15MIN20MIN30MIN45MIN60MIN90MIN
1.60V17712410895.879.468.048.738.427.319.815.811.5
1.67V15611410090.277.665.248.438.127.019.715.711.4
1.70V14710996.887.876.463.947.637.726.919.615.611.3
1.75V13110291.082.972.861.146.237.026.319.315.511.2
1.80V11592.583.777.267.758.044.035.525.518.815.211.1
1.85V98.682.976.070.860.853.340.732.623.817.814.510.6
Constant Power Discharge Characteristics Unit: W (25℃, 77℉)
F.V/Time2MIN4MIN5MIN6MIN8MIN10MIN15MIN20MIN30MIN45MIN60MIN90MIN
1.60V1701128211431041868753544429309227183133
1.67V157011931076989850734540428307226182132
1.70V150911551044962838726534426305225181131
1.75V13981087987913802704520416300222179130
1.80V12821011926862756665501402295219177129
1.85V1166926853797687608461375277207168124
0