Sales hotline:13775032303
**Specification**
- **Cells Per Unit:** 6
- **Voltage Per Unit:** 12 V
- **Capacity:** 88Ah @ 20 hr-rate to 1.75V per cell @ 25°C (77°F)
- **Weight:** Approx. 29.7 kg (65.46 lbs)
- **Maximum Discharge current:** 800A (5 sec)
- **Internal Resistance:** Approx. 3.6 mΩ
- **Operating Temperature Range:**
- Discharge: -15℃~50℃ (5°F~122°F)
- Charge: -15℃~40℃ (5°F~104°F)
- Storage: -15℃~40℃ (5°F~104°F)
- **Nominal Operating Temperature Range:** 25°C ± 3°C (77°F ± 5°F)
- **Float charging voltage:** 13.5 to 13.8 VDC/unit Average at 25°C (77°F)
- **Recommended Maximum Charging current limit:** 26.4A
- **Equalization and Cycle Service:** 14.4 to 15.0 VDC/unit Average at 25°C (77°F)
- **Self Discharge:** It should be more than 75% of the capacity that before storage after stocked for 6 months at ambient temp. 25℃
- **Terminal:** I2-Thread lead alloy recessed terminal to accept M6 bolt
- **Container Material:** Polypropylene(UL 94-HB) & Flammability resistance of (UL 94-V0) can be available upon request.
GPL series
GPL 12880
Valve Regulated Lead Acid Battery
Maintenance-Free Sealed Lead Acid Battery.
Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99%.
General Design for Standby Power Applications
【Design Life】【Float Charging Voltage】
Up to 10 Years in Standby Service at 25℃13.5 ~ 13.8 VDC/Unit at 25℃ (77℉)
Eurobat (20℃) : >12 YEARS VERY LONG LIFE【Equalization Charging Voltage】
【Operating Temperature Range】14.4 ~ 15.0 VDC/Unit at 25℃ (77℉)
Nominal Operating Temperature: 25℃ (77℉)【Self Discharge】
Discharge: -15℃ ~ 50℃ (5℉ ~ 122℉)Less than 10% after 90 days, can be stored up to 6 months at 25℃ (77℉);
Charge: -15℃ ~ 40℃ (5℉ ~ 104℉)Fully recharging is required before usage, and charged sooner if stored
Storage: -15℃ ~ 40℃ (5℉ ~ 104℉)at higher temperature than 25℃ (77℉).
SpecificationDesign according to IEC 60896-21/22:2004
Constant Current Discharge Characteristics Unit: A (25℃, 77℉)
F.V/Time5MIN10MIN15MIN30MIN60MIN90MIN2HR3HR5HR8HR10HR20HR
1.60V34923217510362.845.536.325.617.011.39.214.87
1.67V32122517110262.445.236.025.516.911.29.124.84
1.70V31121916910161.444.835.725.216.811.19.104.83
1.75V27419916399.060.343.935.125.116.611.08.964.74
1.80V24618615496.158.843.134.624.616.210.88.854.66
1.85V21517013890.355.841.032.923.815.810.48.514.48
Constant Power Discharge Characteristics Unit: W (25℃, 77℉)
F.V/Time5MIN10MIN15MIN30MIN60MIN90MIN2HR3HR5HR8HR10HR20HR
1.60V353524961941117772053543430620313611058.3
1.67V330724171919116971953142830520213510957.9
1.70V320223731888116671652942630420113410857.8
1.75V299522611828114570752442430120013210757.5
1.80V278221291734111369451641829819813010657.1
1.85V243419551581106167149540028719012510355.3
0
Contact: Sir SHU
Phone: 13775032303
Tel: 4001177032
Email: 13775032303@139.com
Add: Room 3208, Floor 2, Rongyu Building, No. 780 Wanhangdu Road, Jing'an District, Shanghai