Specifications
Cells Per Unit: 6
Voltage Per Unit: 12 V
Capacity: 80Ah @ 20 hr-rate to 1.75V per cell @ 25°C (77°F)
Weight: Approximately 25.60 Kg (56.42 lbs)
Maximum Discharge Current: 800A (5sec)
Internal Resistance: Approximately 4.0mΩ
Operating Temperature Range:
- Discharge: -15°C to 50°C (5°F to 122°F)
- Charge: -15°C to 40°C (5°F to 104°F)
- Storage: -15°C to 40°C (5°F to 104°F)
Nominal Operating Temperature Range: 25°C ± 3°C (77°F ± 3°F)
Float Charging Voltage: 13.5 to 13.8 VDC/unit Average at 25°C (77°F)
Recommended Maximum Charging Current Limit: 24.0A
Equalization and Cycle Service: 14.4 to 15.0 VDC/unit Average at 25°C (77°F)
Self Discharge: It should be more than 75% of the capacity that before storage after stocked for 6 months at ambient temp. 25°C
Terminal: I2 thread lead alloy terminal to accept M6 bolt
Container Material: PP (UL 94-HB) & Flame Retardant (94-V0) available upon request
**GPL Series**
**GPL 12800G**
**Valve Regulated Lead Acid Battery**
**Maintenance-Free Sealed Lead Acid Battery.**
**Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99%.**
**General**
**Design for Standby Power Applications**
**[Design Life]** **[Float Charging Voltage]**
Up to 10 Years in Standby Service at 25°C13.5 ~ 13.8 VDC/Unit at 25°C (77°F)
Eurobat (20°C): >12 YEARS VERY LONG LIFE**[Equalization Charging Voltage]**
**[Operating Temperature Range]**14.4 ~ 15.0 VDC/Unit at 25°C (77°F)
Nominal Operating Temperature: 25°C (77°F)**[Self Discharge]**
Discharge: -15°C ~ 50°C (5°F~122°F)Less than 10% after 90 days, can be stored up to 6 months at 25°C (77°F);
Charge: -15°C ~ 40°C (5°F~104°F)Fully recharging is required before usage, and charged sooner if stored
Storage: -15°C ~ 40°C (5°F~104°F)at higher temperature than 25°C (77°F).
**Specification**Designed according to IEC 60896-21/22:2004
**Nominal Voltage**12V (6 cells per unit)
**Nominal Capacity**80 Ah @ 20hr-rate to 1.75V per cell @ 25°C (77°F)
**Weight**Approx. 25.60 Kg (56.42 lbs)
**Maximum Discharge Current**800A (5sec)
**Internal Resistance**Approx. 4.0mΩ
**Short Circuit Current**1933A
**Maximum Charge Current**24.0A
**Terminal types**I2 thread lead alloy terminal to accept M6 bolt
**Terminal tightening torque**51.7±10.3 Kgf·cm / 44.9±9.0 Lbf·in / 5.10±1.0 N·m
**Container Material**PP (UL 94-HB) & Flame Retardant (94-V0) available upon request
**Length (L)**277.0±2.5 mm(10.91±0.10 inches)
**Width (W)**168.5±2.0 mm(6.63±0.08 inches)
**Dimensions**
**Container Height (h)**210.5±2.5 mm(8.29±0.10 inches)
**Overall Height (H)**213.5±2.5 mm(8.41±0.10 inches)
**Constant Current Discharge Characteristics** Unit: A (25°C, 77°F)
F.V/Time5MIN10MIN15MIN30MIN60MIN90MIN2HR3HR5HR8HR10HR20HR
1.60V29819814987.553.538.830.921.914.59.577.854.15
1.67V27419114686.753.238.630.721.714.49.467.784.13
1.70V26518714486.152.438.130.521.514.39.407.764.11
1.75V23417013984.451.437.429.921.414.19.387.634.04
1.80V21015813181.950.236.829.521.013.89.177.553.97
1.85V18314511877.047.534.928.120.313.58.887.263.82
**Constant Power Discharge Characteristics** Unit: W (25°C, 77°F)
F.V/Time5MIN10MIN15MIN30MIN60MIN90MIN2HR3HR5HR8HR10HR20HR
1.60V301321271654100361445637026117311693.549.7
1.67V28182060163599661245236526017211592.949.4
1.70V27292022160999461045036325917111492.749.3
1.75V25531927155897660344736125717011392.349.0
1.80V23711815147894959244035625416811191.048.7
1.85V20751667134890457242234124516210787.547.1
0
Contact: Sir SHU
Phone: 13775032303
Tel: 4001177032
Email: 13775032303@139.com
Add: Room 3208, Floor 2, Rongyu Building, No. 780 Wanhangdu Road, Jing'an District, Shanghai