Number of rounds 6
Voltage value 12 V
Ampere 17 Ah @ 20hr rate to 1.75V per cell @ 25 ° C (77 ° F)
Weight Approval. 5.5 kg. (12.12 lbs.)
Maximum discharge current 230 A (5 seconds.)
Internal resistance Approx. 14.0 m Ω
Temperature working range Discharge: -15 ℃~50 ℃ (5 ° F~122 ° F)
Charge: -15 ℃~40 ℃ (5 ° F~104 ° F)
Storage: -15 ℃~40 ℃ (5 ° F~104 ° F)
General operating temperature range: 25 ° C ± 3 ° C (77 ° F ± 5 ° F)
Float charging uses a charging voltage of 13.5 to 13.8 VDC/unit Average at 25 ° C (77 ° F)
Suggested maximum charging current of 5.1A
Average charging voltage of 14.4 to 15.0 VDC/unit at 25 ° C (77 ° F)
It should be more than 75% of the capacity that before storage after stocked for 6 months at ambient temperature
Terminals B1/B3-L to accept M5 nut&bolt
ABS (UL94-HB)&Flammability resistance of (UL94-V0) can be available upon request “
"GP series
GP 12170"
"Valve Regulated Lead Acid Battery
Maintenance‐Free Sealed Lead Acid Battery.
Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99%."
General Design for Standby Power Applications
"【Design Life】
Up to 5 Years in Standby Service at 25℃
Eurobat (20℃) : 3‐5 YEARS STANDARD COMMERCIAL
【 Operating Temperature Range】
Nominal Operating Temperature : 25℃(77℉)
Discharge : ‐15℃ ~ 50℃ (5℉~122℉) Charge: ‐15℃ ~ 40℃ (5℉~104℉) Storage: ‐15℃ ~ 40℃ (5℉~104℉)" "【 Float Charging Voltage】
13.5 ~ 13.8 VDC/Unit at 25℃ (77℉)
【Equalization Charging Voltage 】
14.4 ~ 15.0 VDC/Unit at 25℃ (77℉)
【 Self Discharge】
Less than 10% after 90 days, can be stored up to 6 months at 25℃ (77℉);
Fully recharging is required before usage, and charged sooner if stored at higher temperature than 25℃ (77℉)."
Specification Design according with IEC 61056‐1/2:2012
"Nominal Voltage 12V (6 cells per unit)
Nominal Capacity 17 Ah @20hr‐rate to 1.75V per cell @25℃ (77℉)
Weight Approx. 5.50 Kg (12.12 lbs) Maximum Discharge Current 230A (5sec)
Internal Resistance Approx. 14.0mΩ
Short Circuit Current 532A
Maximum Charge Current 5.10A
Terminal types B1/B3/B1B terminal to accept M5 bolt Terminal tightening torque 30.4±6.1 Kgf∙cm / 26.4±5.3 Lbf∙in / 3.0±0.6 N∙m
Container Material ABS (UL 94‐HB) & Flame Retardant (94‐V0) available upon request
Length (L) 181.0±2.0 mm 7.13±0.08 inch
Width (W) 76.2±1.0 mm 3.00±0.04 inch
Dimensions
Container Height (h) 167.0±2.0 mm 6.57±0.08 inch
Overall Height (H) 167.0±2.0 mm 6.57±0.08 inch"
Constant Current Discharge Characteristics Unit: A (25℃, 77℉)
F.V/Time 5 MIN 10MIN 15MIN 30MIN 60MIN 90MIN 2HR 3HR 5HR 8HR 10HR 20HR
1.60V 80.2 50.9 38.5 23.4 13.8 10.1 8.03 5.72 3.63 2.37 1.93 1.00
1.67V 71.2 47.5 36.5 22.9 13.7 10.0 7.99 5.69 3.61 2.35 1.90 0.95
1.70V 67.4 45.8 35.6 22.7 13.6 9.99 7.97 5.67 3.60 2.34 1.89 0.94
1.75V 61.0 43.1 34.1 22.3 13.4 9.86 7.92 5.64 3.59 2.32 1.86 0.91
1.80V 54.5 40.2 32.7 21.8 13.3 9.79 7.87 5.61 3.58 2.30 1.83 0.88
1.85V 48.0 37.3 31.0 21.2 13.1 9.68 7.80 5.56 3.56 2.27 1.80 0.85
Constant Power Discharge Characteristics Unit: W (25℃, 77℉)
F.V/Time 5MIN 10MIN 15MIN 30MIN 60MIN 90MIN 2HR 3HR 5HR 8HR 10HR 20HR
1.60V 890 583 449 281 166 121 96.4 68.6 43.6 28.4 23.1 12.0
1.67V 790 544 423 275 164 120 96.0 68.5 43.4 28.3 22.8 11.5
1.70V 748 527 413 272 163 119 95.8 68.4 43.3 28.2 22.7 11.3
1.75V 677 493 395 267 161 119 95.3 67.9 43.2 27.9 22.4 10.9
1.80V 605 460 377 261 160 118 94.6 67.3 43.0 27.6 22.0 10.5
1.85V 533 427 361 254 158 116 93.8 66.8 42.9 27.3 21.7 10.1
0