Specification sheet
Number of rounds 6
Voltage value 12 V
Ampere rating 34 Ah @ 20hr rate to 1.75V per cell @ 25 ° C (77 ° F)
Weight: 10.48kg (23.10 lbs.)
Maximum discharge current 380A (5sec.)
Internal resistance Approx. 9.5 m Ω
Temperature working range Discharge: -15 ℃~50 ℃ (5 ° F~122 ° F)
Charge: -15 ℃~40 ℃ (5 ° F~104 ° F)
Storage: -15 ℃~40 ℃ (5 ° F~104 ° F)
General operating temperature range: 25 ° C ± 3 ° C (77 ° F ± 5 ° F)
Float charging uses a charging voltage of 13.5 to 13.8 VDC/unit Average at 25 ° C (77 ° F)
Suggested maximum charging current of 10.2A
Average charging voltage of 14.4 to 15.0 VDC/unit at 25 ° C (77 ° F)
It should be more than 75% of the capacity that before storage after stocked for 6 months at ambient temperature
Terminal B5-L to accept M6 nut&bolt
ABS (UL94-HB)&Flammability resistance of (UL94-V0) can be available upon request “
"GP series
GP 12340"
"Valve Regulated Lead Acid Battery
Maintenance‐Free Sealed Lead Acid Battery.
Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99%."
General Design for Standby Power Applications
"【Design Life】
Up to 5 Years in Standby Service at 25℃
Eurobat (20℃) : 3‐5 YEARS STANDARD COMMERCIAL
【 Operating Temperature Range】
Nominal Operating Temperature : 25℃(77℉)
Discharge : ‐15℃ ~ 50℃ (5℉~122℉) Charge: ‐15℃ ~ 40℃ (5℉~104℉) Storage: ‐15℃ ~ 40℃ (5℉~104℉)" "【 Float Charging Voltage】
13.5 ~ 13.8 VDC/Unit at 25℃ (77℉)
【Equalization Charging Voltage 】
14.4 ~ 15.0 VDC/Unit at 25℃ (77℉)
【 Self Discharge】
Less than 10% after 90 days, can be stored up to 6 months at 25℃ (77℉);
Fully recharging is required before usage, and charged sooner if stored at higher temperature than 25℃ (77℉)."
Specification Design according with IEC 61056‐1/2:2012
"Nominal Voltage 12V (6 cells per unit)
Nominal Capacity 34 Ah @20hr‐rate to 1.75V per cell @25℃ (77℉)
Weight Approx. 10.48 Kg (23.10 lbs) Maximum Discharge Current 380A (5sec)
Internal Resistance Approx. 9.5mΩ
Short Circuit Current 915A
Maximum Charge Current 10.20A
Terminal types B5 terminal to accept M6 bolt
Terminal tightening torque 51.7±10.3 Kgf∙cm / 44.9±9.0 Lbf∙in / 5.10±1.0 N∙m
Container Material ABS (UL 94‐HB) & Flame Retardant (94‐V0) available upon request
Length (L) 195.6±2.0 mm 7.70±0.08 inch
Width (W) 130.0±1.5 mm 5.12±0.08 inch
Dimensions
Container Height (h) 154.8±2.0 mm 6.09±0.08 inch
Overall Height (H) 178.3±2.0 mm 7.02±0.08 inch"
Constant Current Discharge Characteristics Unit: A (25℃, 77℉)
F.V/Time 5 MIN 10MIN 15MIN 30MIN 60MIN 90MIN 2HR 3HR 5HR 8HR 10HR 20HR
1.60V 148 101 75.0 43.2 24.9 18.0 14.3 10.3 6.66 4.40 3.60 1.91
1.67V 134 95.5 72.8 42.6 24.7 17.9 14.2 10.2 6.62 4.37 3.58 1.90
1.70V 127 91.9 71.4 42.2 24.5 17.8 14.1 10.1 6.60 4.36 3.57 1.89
1.75V 112 84.2 67.9 41.1 24.1 17.6 14.0 10.0 6.54 4.33 3.55 1.88
1.80V 99.9 75.6 62.4 39.3 23.4 17.1 13.7 9.91 6.43 4.26 3.49 1.86
1.85V 84.3 68.4 55.5 36.8 22.1 16.3 13.1 9.52 6.18 4.10 3.36 1.79
Constant Power Discharge Characteristics Unit: W (25℃, 77℉)
F.V/Time 5MIN 10MIN 15MIN 30MIN 60MIN 90MIN 2HR 3HR 5HR 8HR 10HR 20HR
1.60V 1458 1057 822 517 302 217 172 123 79.4 52.6 43.1 23.0
1.67V 1339 1014 804 511 299 216 171 122 79.1 52.4 43.0 22.9
1.70V 1284 986 792 506 297 215 170 121 79.0 52.3 42.8 22.8
1.75V 1198 925 757 494 293 213 169 120 78.4 52.0 42.6 22.7
1.80V 1088 852 702 475 285 209 167 119 77.4 51.3 42.1 22.5
1.85V 950 786 639 448 268 199 161 115 74.8 49.7 40.8 21.8