Sales hotline:13775032303
Specification
- Cells Per Unit: 6
- Voltage Per Unit: 12 V
- Capacity: 34W @ 15-minute rate to 1.67V per cell @ 25°C (77°F)
- Weight: Approximately 2.50 kg (5.51 lbs)
- Maximum Discharge Current: 100/130A (5 sec)
- Internal Resistance: Approximately 19mΩ
- Operating Temperature Range:
- Discharge: -15℃~50℃ (5°F~122°F)
- Charge: -15℃~40℃ (5°F~104°F)
- Storage: -15℃~40℃ (5°F~104°F)
- Nominal Operating Temperature Range: 25°C ± 3°C (77°F ± 5°F)
- Float Charging Voltage: 13.5 to 13.8 VDC/unit on average at 25°C (77°F)
- Recommended Maximum Charging Current Limit: 3.4A
- Equalization and Cycle Service: 14.4 to 15.0 VDC/unit on average at 25°C (77°F)
- Self Discharge: It should be more than 75% of the capacity before storage after being stocked for 6 months at ambient temperature of 25℃
- Terminal: F2 - Faston Tab250
- Container Material: ABS (UL94-HB) & Flammability resistance of (UL94-V0) can be available upon request.
HR series
HR 1234W
Valve Regulated Lead Acid Battery
Maintenance-Free Sealed Lead Acid Battery.
Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99%.
GeneralDesign for Standby Power Applications
【Design Life】【 Float Charging Voltage】
Up to 5 Years in Standby Service at 25℃13.5 ~ 13.8 VDC/Unit at 25℃ (77℉)
Eurobat (20℃) : 3-5 YEARS STANDARD COMMERCIAL【Equalization Charging Voltage 】
【 Operating Temperature Range】14.4 ~ 15.0 VDC/Unit at 25℃ (77℉)
Nominal Operating Temperature : 25℃(77℉)【 Self Discharge】
Discharge : -15℃ ~ 50℃ (5℉~122℉)Less than 10% after 90 days, can be stored up to 6 months at 25℃ (77℉);
Charge: -15℃ ~ 40℃ (5℉~104℉)Fully recharging is required before usage, and charged sooner if stored
Storage: -15℃ ~ 40℃ (5℉~104℉)at higher temperature than 25℃ (77℉).
SpecificationDesign according with IEC 61056-1/2:2012
Nominal Voltage12V (6 cells per unit)
Nominal Capacity34W @15min-rate to 1.67V per cell @25℃ (77℉)
WeightApprox. 2.50 Kg (5.51 lbs)
Maximum Discharge Current130A (5sec)
Internal ResistanceApprox. 19.0 mΩ
Short Circuit Current349A
Maximum Charge Current3.4A
Terminal typesF2 -Faston Tab250
Terminal tightening torque--
Container MaterialABS (UL 94-HB) & Flame Retardant (94-V0) available upon request
Length (L)150.9±2.0mm5.94±0.08inch
Width (W)64.8±1.0mm2.55±0.04inch
Dimensions
Container Height (h)94.3±1.0mm3.71±0.04inch
Overall Height (H)98.6±1.0mm3.88±0.04inch
Constant Current Discharge Characteristics Unit: A (25℃, 77℉)
F.V/Time2MIN4MIN5MIN6MIN8MIN10MIN15MIN20MIN30MIN45MIN60MIN90MIN
1.60V74.050.042.236.829.624.918.014.210.37.365.844.21
1.67V67.347.540.735.829.024.517.814.110.27.345.824.20
1.70V64.145.939.735.228.624.217.714.010.17.335.814.19
1.75V58.342.837.533.627.623.517.413.910.07.275.774.17
1.80V52.639.134.731.226.022.416.813.59.837.125.674.11
1.85V46.235.431.228.223.820.615.712.79.386.835.453.96
Constant Power Discharge Characteristics Unit: W (25℃, 77℉)
F.V/Time2MIN4MIN5MIN6MIN8MIN10MIN15MIN20MIN30MIN45MIN60MIN90MIN
1.60V73751845039932828020716512086.769.050.1
1.67V68850243839132427720616411986.568.950.0
1.70V67749243138632027520516311886.368.849.9
1.75V63346641337231226820216111785.768.449.8
1.80V58443438835129825719615711684.367.449.2
1.85V51939735532427624018515011181.365.247.8
0
Contact: Sir SHU
Phone: 13775032303
Tel: 4001177032
Email: 13775032303@139.com
Add: Room 3208, Floor 2, Rongyu Building, No. 780 Wanhangdu Road, Jing'an District, Shanghai