Sales hotline:13775032303
Specification
Cells Per Unit: 6
Voltage Per Unit: 12 V
Capacity: 1129W @ 5min-rate to 1.60V per cell @25°C (77°F)
Weight: Approx. 47.90 Kg (105.57 lbs)
Maximum Discharge Current: 1350A
Internal Resistance: Approx. 2.33 mΩ
Operating Temperature Range:
- Discharge: -15℃~50℃ (5°F~122°F)
- Charge: -15℃~40℃ (5°F~104°F)
- Storage: -15℃~40℃ (5°F~104°F)
Nominal Operating Temperature Range: 25°C±3°C (77°F±5°F)
Float Charging Voltage: 13.5 ~ 13.8 VDC/Unit at 25℃ (77℉)
Recommended Maximum Charging Current Limit: 55.8A
Equalization and Cycle Service: 14.4 ~ 15.0 VDC/Unit at 25℃ (77℉)
Self Discharge: Less than 10% after 90 days, can be stored up to 6 months and 10 months with equalization charge at 25℃ (77℉)
Terminal: I2 thread lead alloy terminal to accept M6 bolt
Container Material: PP (UL 94-HB) & Flame Retardant (94-V0) available upon request
XPL series
XPL6700
Valve Regulated Lead Acid Battery
Maintenance-Free Sealed Lead Acid Battery.
Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99%.
GeneralDesigned for Standby Power Applications
【Design Life】【Float Charging Voltage】
Up to 10 Years in Standby Service at 25℃13.5 ~ 13.8 VDC/Unit at 25℃ (77℉)
Eurobat (20℃): >12 YEARS VERY LONG LIFE【Equalization Charging Voltage】*
【Operating Temperature Range】14.4 ~ 15.0 VDC/Unit at 25℃ (77℉)
Nominal Operating Temperature: 25℃ (77℉)【Self Discharge】
Discharge: -15℃ ~ 50℃ (5℉~122℉)Less than 10% after 90 days, can be stored up to 6 months and 10 months
Charge: -15℃ ~ 40℃ (5℉~104℉)with equalization charge* at 25℃ (77℉);
Storage: -15℃ ~ 40℃ (5℉~104℉)Full recharging is required before usage, and charged sooner if stored
at a higher temperature than 25℃ (77℉).
SpecificationDesigned according to IEC 60896-21/22:2004
Nominal Voltage12V (6 cells per unit)
Nominal Capacity6700W @5min-rate to 9.60V per PCS @25℃ (77℉)
WeightApprox. 47.90 Kg (105.57 lbs)
Maximum Discharge Current1350A
Internal ResistanceApprox. 2.33 mΩ
Short Circuit Current4018A
Maximum Charge Current55.8A
Terminal typesI2 thread lead alloy terminal to accept M6 bolt
Terminal tightening torque51.7±10.3 Kgf·cm / 44.9±9.0 Lbf·in / 5.1±1.0 N·m
Container MaterialPP (UL 94-HB) & Flame Retardant (94-V0) available upon request
Length (L)343.0±2.5 mm13.50±0.10 inch
Width (W)170.0±2.0 mm6.69±0.08 inch
Dimensions
Container Height (h)273.2±2.5 mm10.76±0.10 inch
Overall Height (H)275.7±2.5 mm10.85±0.10 inch
Constant Current Discharge Characteristics Unit: A (25℃, 77℉)
F.V/Time2MIN4MIN5MIN6MIN8MIN10MIN15MIN20MIN30MIN45MIN60MIN90MIN
1.60V82069164660354147636928920514611581.7
1.67V72562258355249044234927720014411381.3
1.70V68758955652746742533827019714211281.1
1.75V60754050347342839331525519013911180.5
1.80V53846544042238434728823718113310779.1
1.85V41740538436032530025321316712410175.0
Constant Power Discharge Characteristics Unit: W (25℃, 77℉)
F.V/Time2MIN4MIN5MIN6MIN8MIN10MIN15MIN20MIN30MIN45MIN60MIN90MIN
1.60V844072556774634956505092403932612422176213921003
1.67V78406754632959595361488239113179238317401379997
1.70V75526512609457745196478338293124235317241369993
1.75V68576011571854084894445936232984227816811342981
1.80V60775461515549174482408333222776216316121295956
1.85V52214792460443433961363929422505200615071219907
Constant Power Discharge Characteristics Unit: W (25℃, 77℉)
F.V/Time30SEC40SEC50SEC60SEC70SEC80SEC90SEC
1.60V9464933692389159897788238689
1.67V8800858084138279812579937879
1.70V7881776776807610759975897581
0
Contact: Sir SHU
Phone: 13775032303
Tel: 4001177032
Email: 13775032303@139.com
Add: Room 3208, Floor 2, Rongyu Building, No. 780 Wanhangdu Road, Jing'an District, Shanghai